DTFS: a design for side mounting and fully recessed door or side installation Maximum energy efficiency for significant energy savings and reduced operating costs Energy-saving modes included as standard for an even greater reduction inoperating costs Significantly less refrigerant used for a better CO2 footprint F-Gas ready thanks to the use of low GWP refrigerants Perfect service friendliness Version LED - indication of operation status only Modbus interface is optionally available for perfect machine integration
TECHNICAL DATA
Technical Data
- Rated voltage V ±10 %
- AC 400 / 460 V 2~
- Rated frequency Hz ±1 %
- 50 Hz | 60 Hz
- Cooling capacity W
- 870 W | 940 W
- Cooling capacity according to EN 14511 (A35/A50) W
- 690 W | 730 W
- Power consumption (A35/A35) W
- 440 W | 440 W
- Current consumption (A35/A35)
- 1,3 A | 1,3 A
- Starting current (A35/A35) A
- 3,2 A | 2,8 A
- Unimpeded internal airflow (free flow) m³/h
- 290 m3/h
- Unimpeded external airflow (free flow) m³/h
- 540 m3/h
- Controller
- LED
- Type of connection
- spring-type terminal included with plug
- Ambient temperature °C
- +15 °C ... +55 °C
- Control range (adjustable) °C
- +25 °C ... +50 °C
- Refrigerant (type | amount)
- R513A | 225 g
- Condensate management
- condensate drain
- IP Protection
- IP 55
- NEMA Protection
- TYPE12
- Protection system according to EN 60529 towards the surroundings
- IP 24
- Design housing
- electrostatically powder coated (200C)
- Design cover
- electrostatically powder coated (200C)
- Colour
- RAL 7035
- Mounting position
- Side Mount or Fully Recessed
- Dimensions (H | W | D) mm
- 550 mm | 280 mm | 280 mm
- Installation depth mm
- 260 mm
- ETIM-Class
- EC000855
- Rated voltage V ±10 %
- AC 400 / 460 V 2~
- Rated frequency Hz ±1 %
- 50 Hz | 60 Hz
- Cooling capacity according to EN 14511 (A35/A35)
- 2,969 BTU/h | 3,207 BTU/h
- Cooling capacity according to EN 14511 (A35/A50)
- 2,354 BTU/h | 2,491 BTU/h
- Power consumption (A35/A35)
- 440 W | 440 W
- Current consumption (A35/A35)
- 1.3 A | 1.3 A
- Starting current (A35/A35)
- 3.2 A | 2.8 A
- Unimpeded internal airflow (free flow)
- 171 cfm
- Unimpeded external airflow (free flow)
- 318 cfm
- Controller
- LED
- Type of connection
- spring-type terminal included with plug
- Weight (without packaging)
- 55.1 lbs
- Ambient temperature range
- +59 °F ... +131 °F
- Control range (adjustable)
- +77 °F ... +122 °F
- Refrigerant (type | amount)
- R513A | 7.94 oz.
- Condensate management
- condensate drain
- IP Protection
- IP 55
- NEMA Protection
- TYPE12
- Protection system according to EN 60529 towards the surroundings
- IP 24
- Design housing
- electrostatically powder coated (200C)
- Design cover
- electrostatically powder coated (200C)
- Colour
- RAL 7035
- Mounting position
- Side Mount or Fully Recessed
- Dimensions (H | W | D)
- 21.65 in. | 11.02 in. | 11.02 in.
- Installation depth
- 10.24 in.
- ETIM-Class
- EC000855
Technical Data
TECHNICAL DRAWINGS
Technical Drawings
Dimensions
DIAGRAMS
Diagrams
DOWNLOADS
Downloads
Description | Language | Type | Size | Link |
---|---|---|---|---|
3D-models_STEP_DTFS | Englisch | tables.type.files_zip | 338.97 KB | Download |
ePLAN_Macros_DTFS | German | tables.type.files_zip | 3.11 MB | Download |
Cut-out_DXF_DTFS60x1 | German | tables.type.files_zip | 14.76 KB | Download |
3D-models_STEP_DTFS | German | tables.type.files_zip | 338.97 KB | Download |
Manual_DTFS_DE_EN | German | 23.71 MB | Download | |
Product_Sheet_DE_DTFS_6041 | German | 378.64 KB | Download | |
ePLAN_Macros_DTFS | Englisch | tables.type.files_zip | 3.11 MB | Download |
Cut-out_DXF_DTFS60x1 | Englisch | tables.type.files_zip | 14.76 KB | Download |
Manual_DTFS_DE_EN | Englisch | 23.71 MB | Download | |
Product_Sheet_EN_DTFS_6041 | Englisch | 378.46 KB | Download | |
UL_Certificate_DTFS | Englisch | 285.37 KB | Download |