Technical Data


Technical Data
Rated voltage V ±10 %
AC 400 V2~
Rated frequency Hz ±1 %
50 Hz | 60 Hz
Cooling cap. W at l/h
1500 W @ 200 l/h
Power consumption (W10/A35) W
77 W | 76 W
Current consumption (W10/A35) A
0,35 A | 0,35 A
Starting current (W10/A35) A
0,49 A | 0,59 A
Type of fuse | Pre fuse
gG | 2 A
Type of connection (electro)
spring-type terminal included with plug
Type of connection (fluid)
13 mm Hose Nozzle, Other Connectors On Request
Weight (without packaging) kg
17,4 kg
Ambient temperature °C
+1 °C ... +70 °C
Control range (adjustable) °C
+8 °C ... +50 °C
Water inlet temperature °C
> +1 °C ... +35 °C
Permissible operating pressure bar
max. 10 bar
Condensate management
condensate drain
Protection system according to EN 60529 towards the electrical enclosure
IP 55
Design housing
Galvanised Steel, Electrostatically Powder Coated (200C)
Design heat exchanger
copper pipe with aluminium fins
Colour
RAL 7035
Mounting position
Side Mount
Dimensions (H | W | D) mm
938 mm | 410 mm | 142 mm
Installation depth mm
60 mm
UL-file numbers
SA33060
ETIM-Class
EC002515
Rated voltage V ±10 %
AC 400 V2~
Rated frequency Hz ±1 %
50 Hz | 60 Hz
Cooling capacity @ flow rate (W10/A35)
5118 BTU @ 200 l/h
Power consumption (W10/A35)
77 W | 76 W
Current consumption (W10/A35)
0.35 A | 0.35 A
Starting current (W10/A35)
0.49 A | 0.59 A
Type of fuse | Pre fuse
gG | 2 A
Type of connection (electro)
spring-type terminal included with plug
Type of connection (fluid)
13 mm Hose Nozzle, Other Connectors On Request
Weight (without packaging)
37 lbs
Ambient temperature range
+34 °F ... +158 °F
Control range (adjustable)
+46 °F ... +122 °F
Water inlet temperature
> +34 °F ... +95 °F
Permissible operating pressure
max. 145 psi
Condensate management
condensate drain
Protection system according to EN 60529 towards the electrical enclosure
IP 55
Design housing
Galvanised Steel, Electrostatically Powder Coated (200C)
Design heat exchanger
copper pipe with aluminium fins
Colour
RAL 7035
Mounting position
Side Mount
Dimensions (H | W | D)
36.9 in. | 16.1 in. | 5.6 in.
Installation depth
2.36 in.
UL-file numbers
SA33060
ETIM-Class
EC002515

Technical Drawings

Dimensions
A
662 mm
B
320 mm
C
350 mm
D
280 mm
E
282 mm
F
55 mm
X
410 mm
Y
945,5 mm
Z
142 mm
A
26,06 in
B
12,6 in
C
13,78 in
D
11,02 in
E
11,1 in
F
2,17 in
X
16,14 in
Y
37,22 in
Z
5,59 in

Mounting holes Ø 8 mm and cut-out radii R20

Diagrams

Downloads

Description Type Size Link
Conformity PWS 7002 - 71002 PDF 354.45 KB Download
Conformity PWS 7002 - 71002 PDF 73.18 KB Download
Short operat. instruction PDF 1000.75 KB Download
Short operat. instruction PDF 1000.75 KB Download
Op. inst. PWx 6152 400V 460V PDF 3.34 MB Download
Op. inst. PWx 6152 400V 460V PDF 2.86 MB Download
CE DECLARATION PDF 226.05 KB Download
CE DECLARATION PDF 231.67 KB Download
Description Language Type Size Link
UL_Certificate_PWx_6xxx German PDF 378.1 KB Download
Product_Sheet_EN_PWI_PWS_6152 Englisch PDF 218.2 KB Download
UL_Certificate_PWx_6xxx Englisch PDF 378.1 KB Download
Cut-out_DXF_PWI_6052_6102 German ZIP 6.72 KB Download
3D-model_STEP_PWI6152_6302c German ZIP 1.5 MB Download
EAC_Certificate_PW German PDF 1.64 MB Download
3D-model_STEP_PWI6152_6302c Englisch ZIP 1.5 MB Download
Cut-out_DXF_PWI_6052_6102 Englisch ZIP 6.72 KB Download
Product_Sheet_DE_PWI_PWS_6152 German PDF 218.46 KB Download
EAC_Certificate_PW Englisch PDF 1.64 MB Download